BCK Contracting Ltd 2019 Copyright©  

All Rights Reserved

PRIVACY POLICY

Plumis Automist® Tap Head

The Tap Head is not LABC Registered and is not typically used for building regulation compliance unless supported with a Fire Engineering Justification.
Technical Details

Water flow 

- 5.6 litres per minute

Trigger 

- conventional 57°C heat
detector and/or optional manual call point

Protected Area 

- 32m² area protection per pump with fire hazards up to 5m away from each spray head

Run time 

- 30 mins default or configurable with a fire panel

Installation Requirements 

- Reliable water supply (6 lpm flow and 1 -10 bar pressure) connected with a standard BSP ¾” fitting. 230V/50Hz electrical supply on an independent circuit using a C16 breaker

Tap Compatibility

The head has been desinged to be compatible with the majority of Mono bloc taps (45 - 60mm Diameter base) that fit into a standard 35mm sink or work surface hole.

Room Compatibility

A single Pump and Head will cover an area of 32m² (2.5m ceiling height) with fire hazards up to 5m away. 

Accredited automist Installer

Automist® Smartscan® are the registered trademark of Plumis Ltd.

Plumis Ltd Copyright© 2016

Fire Prevention

Fire Protection

Fire Solutions